Troubleshooting

Possible reasons for the malfunction
  • Power Failure
  • Power wire loose
  • Control power fuses broken
  • High and low pressure protection switch short-circuit
  • AC circuit devices or circuit board failure
Solutions
  • Disconnect the power switch, check the main circuit, power supply, voltage, whether there is electricity, or lack of phase
  • Identify the causes and fixes
  • Change new fuses
  • Fix or change the switch
  • Fix or change circuit board

Possible reasons for the malfunction
  • Lacking water in Water systems ◇Air in Water systems
  • Some water valves closed ◇Blocked or dirty filters
Solutions
  • Inspect the water system, and replenish it
  • Release the air
  • Open water valve
  • Remove blockage & wash filters

Possible reasons for the malfunction
  • Refrigerant shortage
  • Bad water system insulation
  • Bad heat exchanger cooling
  • Lack of water flow
  • Filter blocked
Solutions
  • Check leakage and replenish
  • Check the heat preservation
  • Wash air heat exchanger
  • Clean or change filter
  • Clean or change filter

Possible reasons for the malfunction
  • Power supply failure
  • Compressor contactor is damaged
  • Loose wiring
  • Compressor overheat protection
  • High and low pressure protection switch short-circuit
  • Water overheat protection
  • Lack of water flow
Solutions
  • Identify the causes and correct
  • Change compressor contactor
  • Identify the loose point and correct
  • Check the exhaust temperature protection switch open circuit or not, to identify the reasons for overheating before using
  • Fix or change the switch
  • Reset the outlet water temp
  • Wash filters and release air

Possible reasons for the malfunction
  • Liquid refrigerant into the compressor
  • Insufficient lubrication
  • Compressor internal parts damaged
Solutions
  • Check whether the expansion valve failure
  • Add oil
  • Change Compressor

Possible reasons for the malfunction
  • Fan screw loose
  • Electrical burn
  • Contactor damage
Solutions
  • Tighten fan screw
  • Change the fans
  • Change contactor

Possible reasons for the malfunction
  • Refrigerant totally leaked
  • Compressor Malfunction
Solutions
  • Leakage check and add refrigerant
  • Change compressor

Possible reasons for the malfunction
  • Air in the system caused high pressure increases, which turns off the protection Switch
  • Excessive refrigerant
  • Abnormal power supply voltage or not enough diameter wire, excessive power supply circuits caused small starting current
  • High and low pressure protection switch malfunction or air exhaust temp switch malfunction.
Solutions
  • Vacuum and add refrigerant
  • Discharge excess refrigerant
  • Return to normal power supply
  • Change switch

Possible reasons for the malfunction
  • Excessive refrigerant
  • Air in the system (Air-type non-condensable gas)
  • Lack of water flow
  • Excessive scale in condenser
Solutions
  • Discharge excess refrigerant
  • Discharge non-condensable gas
  • Check water system and increase water flow
  • Clean condense

Possible reasons for the malfunction
  • Lack of refrigerant
  • Circulating water temperature or the ambient temperature is too low
  • Pressure drop through the heat exchanger
Solutions
  • Filling amount of refrigerant
  • After the water is back to the temperature, and then check the pressure
  • Check expansion valve opening

Possible reasons for the malfunction
  • Fan motor malfunction
  • Fan Capacitor Failure
Solutions
  • Fix or change fan motor
  • Change the Fan Capacitor in same model

Possible reasons for the malfunction
  • Compressor coil burnt or inter-turn short-circuit
  • Compressor choked
  • Electrical leakage
Solutions
  • Change Compressor
  • Change Compressor
  • Check lines and electrical appliances